Flexelements; Iec 61580 Goose Analog Values - GE Multilin F35 Instruction Manual

Multiple feeder protection system ur series
Table of Contents

Advertisement

6 ACTUAL VALUES
PATH: ACTUAL VALUES
METERING
FLEXELEMENT 1
The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT™ BASE UNITS
dcmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE ENERGY
(SRC X Positive and Negative
Watthours); (SRC X Positive and
Negative Varhours)
SOURCE POWER
SOURCE THD & HARMONICS
SOURCE VOLTAGE
PATH: ACTUAL VALUES
METERING
IEC 61850
GOOSE ANALOGS
MESSAGE
MESSAGE
The F35 Multiple Feeder Protection System is provided with optional IEC 61850 communications capabil-
ity. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of
chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is
ordered.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
GE Multilin

FLEXELEMENTS

FLEXELEMENT 1(16)
FLEXELEMENT 1
OpSig: 0.000 pu
BASE = maximum value of the
DCMA INPUT MAX
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE
BASE = 1%
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
IEC 61850 GOOSE ANALOGS
ANALOG INPUT
1
0.000
ANALOG INPUT
2
0.000
ANALOG INPUT 16
0.000
F35 Multiple Feeder Protection System
setting for the two transducers configured
× I
for the +IN and –IN inputs
BASE

6.3.5 IEC 61580 GOOSE ANALOG VALUES

6.3 METERING
6.3.4 FLEXELEMENTS™
6-19