Mitsubishi Electric Melsec FX Series Beginners Manual page 74

Programmable logic controllers
Hide thumbs Also See for Melsec FX Series:
Table of Contents

Advertisement

Learning to Use the FX Family for Positioning Control
Function
Writing
parameters to
the inverter
while the PLC is
in RUN mode.
Tab. 4-22: Description of the program example in fig. 4-21
4 - 32
Number
Description
³
The maximum frequency (Pr. 1) is specified
·
The maximum frequency (Pr. 1) is set to "120 Hz"
»
The minimum frequency (Pr. 2) is specified
¿
The minimum frequency (Pr. 2) is set to "5 Hz"
´
The acceleration time (Pr. 7) is specified
²
The acceleration time (Pr. 7) is set to "1 sec"
The deceleration time (Pr. 8) is specified
º
The deceleration time (Pr. 8) is set to "1 sec"
The parameters are written at one time
¾
[Contents of D200–D207
µ
The maximum frequency (Pr. 1) is set to "120 Hz" [K12000
¸
The minimum frequency (Pr. 2) is set to "5 Hz" [K500
¹
The acceleration time (Pr. 7) is set to "1 sec" [K10
The deceleration time (Pr. 8) is set to "1 sec" [K10
Reset driving of write instruction
Pr. 1, Pr. 2, Pr. 7 and Pr. 8]
Pr. 2]
Pr. 7]
Pr. 8]
MITSUBISHI ELECTRIC
Inverter Drive Control
Pr. 1]