Control Board Technical Specifications - Siemens bt300 Operator's Manual

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

Specification
Embedded Protocols
Over voltage trip limit
Under voltage trip limit
Protection features

Control Board Technical Specifications

Terminal
1
+10 Vdc Reference Output
2
Analog Input 1 Signal (+)
3
Analog Input 1 Common (-)
4
Analog Input 2 Signal (+)
5
Analog Input 2 Common (-)
6
24 Vdc Output Voltage
7
I/O Ground
8
Digital Input 1
9
Digital Input 2
10
Digital Input 3
11
Common for DI 1 - DI 6
12
24 Vdc Output Voltage
13
I/O Ground
14
Digital Input 4
15
Digital Input 5
16
Digital Input 6
Siemens Industry, Inc.
Building Technologies
RS-485:
APOGEE P1, BACnet MS/TP, Modbus RTU, Metasys N2
Ethernet:
BACnet IP, Modbus TCP
208 to 240 Vac: 456 Vdc
380 to 500 Vac: 911 Vdc
525 to 600 Vac: 1094 Vdc
Depends on supply voltage (0.8775* supply voltage):
208 Vac: 182.5 Vdc
240 Vac: 210.6 Vdc
380 Vac: 333.5 Vdc
480 Vac: 421.2 Vdc
575 Vac: 504.6 Vdc
Under-voltage trip limit
Over-voltage trip limit
Ground fault protection
Input (mains) supervision
Motor phase supervision
Over-current protection
Unit over-temperature protection
Motor overload protection
Motor stall protection
Motor underload protection
Short-circuit protection of 10 Vdc and 24 Vdc reference voltages
Table 140: Control Module Technical Specifications
Signal/Description
Slot A
Siemens BT300 HVAC Drive
Chapter 6 - Technical Information
Control Board Technical Specifications
Description
Specification
+3%; Maximum current 10 mA
0 through 10 Vdc or 0 through 20 mA (selection with
DIP switch)
Resolution: 0.1%, Accuracy: ±1%
0 through 10 Vdc or 0 through 20 mA (selection with
DIP switch)
Resolution: 0.1%, Accuracy: ±1%
±10%; Maximum 250 mA
Positive or negative logic;
0 Vdc - 5 Vdc = 0; 15 Vdc - 30 Vdc = 1
±10%; Maximum 250 mA
Positive or negative logic;
0 Vdc - 5 Vdc = 0; 15 Vdc - 30 Vdc = 1
175 | 180
DPD01809
2016-06-07