Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

NPT
NPA
BI
4
BI
5
BI
6
BI
7
BI
8
Analog Outputs (AO)
All analog outputs (AO) points have the following features:
Support Change of State (COS) reporting based on override status.
Always considered reliable.
Overriding of the AO points is the method used to change a value. Overriding an AO point with a value beyond
the limit allowed by the drive's internal variable will result in an Invalid Data error and the override status
and value will remain unchanged. If the overridden value is beyond the drive's parameter limit but within the
range that will fit in the variable, an acknowledge response is given and the value will be internally clamped to
its limit.
NPT
NPA
AO
1
AO
2
AO
3
AO
4
AO
5
AO
6
AO
7
AO
8
AO
9
AO
10
AO
11
AO
12
AO
13
AO
14
AO
15
Binary Outputs (BO)
All binary outputs (BO) points have the following features:
Support Change of State (COS) reporting based on override status.
Always considered reliable.
Overriding BO points control the drive. These points are input commands to the drive. When released, the
drive's internal value remains at its last overridden value.
Siemens Industry, Inc.
Building Technologies
Description
Faulted
Alarm
Ref. Frequency reached
Motor running zero speed
Flux ready
Table 92: N2 Analog Outputs.
Description
Comms Speed
Current Limit
Minimum Speed
Maximum Speed
Accel Time
Decel Time
FBProcessDataIn1*
FBProcessDataIn2*
FBProcessDataIn3*
FBProcessDataIn4*
FBProcessDataIn5*
FBProcessDataIn6*
FBProcessDataIn7*
FBProcessDataIn8*
Any parameter Read/Write
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
0 =
Not Faulted
Faulted
Not Alarm
Alarm
False
True
False
True
Not Ready
Ready
Units
%
2 decimal places
A
2 decimal places
Hz
2 decimal places
Hz
2 decimal places
s
1 decimal place
s
1 decimal place
2 decimal places
2 decimal places
2 decimal places
2 decimal places
2 decimal places
2 decimal places
2 decimal places
2 decimal places
Depends on parameter
1 =
Note