Siemens bt300 Operator's Manual page 107

Hvac drive
Hide thumbs Also See for bt300:
Table of Contents

Advertisement

Structure
Parameter
P3.16.5
FireMode FreqSource
P3.16.6
FireMode Reverse
M3.16.7
FireMode Status
M3.16.8
FireMode Counter
Siemens Industry, Inc.
Building Technologies
Unit
Min
Max
FireMode Freq
Motor Pot Ref
Disabled
Test Mode
0
4294967295
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Default
ID
FireMode Freq
1617
Selection of the frequency
reference source to be followed
when fire mode has be activated
as defined by FireMode
Activ.Open (P3.16.2) or
FireMode Activ.Close (P3.16.3).
Possible settings:
0 = Fire Mode Frequency (as
defined by FireMode Freq
(P3.16.4))
1 = Preset Speeds
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1
8 = Motor Potentiometer
DigIN Slot0.1
1618
Defines location of the reverse
command when Fire Mode is
active as defined by FireMode
Activ.Open (P3.16.2) or
FireMode Activ.Close (P3.16.3).
Open Contact = Forward
Contact Closure = Reverse
NOTE: This function has no
effect in normal mode of
operation.
Also see Menu Structure
P3.5.1.4.
Disabled
1597
Displays the status of the Fire
Mode as follows:
0 = Disabled
1 = Enabled
2 = Activated (Enabled and DI
active)
3 = Test Mode
1679
Displays the number of times
the Fire Mode has been
activated.
NOTE: This counter cannot be
reset.
Parameters (M3)
Description
107 | 180
DPD01809
2016-06-07

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents