Technical Data

Specification
Input Voltages and Power Ranges
(3-phase)
Input Frequency
Output Voltage
Output Frequency
Output Frequency Resolution
Efficiency
PWM (switching) frequency
Short circuit withstand rating
Frequency Reference
Analog Input
Keypad
Field weakening point
Acceleration time
Deceleration time
Ambient Operating Temperature
Relative Humidity
Air quality:
Chemical vapors
Mechanical particles
Altitude
Fixed frequencies
Skip (prohibited) frequency band
Vibration
Siemens Industry, Inc.
Building Technologies
Table 139: Drive Specifications.
208 to 240 Vac (-10% to +10%):
1 hp to 125 hp (0.75 kW to 90 kW)
380 to 500 Vac (-10% to +10%):
1.5 hp to 250 hp (1.1 kW to 160 kW)
525 to 600 Vac (-10% to+10%):
3 hp to 200 hp (2.2 kW to 132 kW)
45 to 66 Hz (50 to 60 Hz; -5% to +10%)
0 to Input voltage
0 to 320 Hz
0.01 Hz
>97.5%
FS4 to FS6 - 1.5 to 10 kHz
Default FS4: 6 kHz; FS5: 4 kHz; FS6 = 4 kHz
FS7 to FS9 - 1.5 to 6 kHz
Default FS7: 4 kHz; FS8: 3 kHz; FS9: 2kHz
Adjustable in .1 kHz increments
Automatic switching frequency derating in case of overheating
100,000 AIC
Resolution 0.01 to 0.1% (10 bit), accuracy ±1%
Resolution 0.01 Hz
8 to 320 Hz
0.1 to 3000.0 seconds
0.1 to 3000.0 seconds
14°F (-10°C) (no frost) to 104°F (40°C)
up to 122°F (50°C) with derating
0 to 95% rh, non-condensing, non-corrosive
IEC 60068-2-60 (H
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S3.
100% load capacity (no-derating) up to 3,280 ft (1,000 m)
-1% derating for each 328 ft (100 m) above 3,280 ft (1,000 m)
Maximum altitude:
208 to 240 Vac: 13,123 ft (4,000 m)
380 to 500 Vac: 13,123 ft (4,000 m)
525 to 600 Vac: 6,562 ft (2,000 m)
Voltage for relay outputs:
240 Vac: ≤ 9,842 ft (3,000 m)
120 Vac: ≤ 13,123 ft (4,000 m)
Corner-grounding (380 through 500 Vac systems only):
≤ 6,562 ft (2,000 m)
7 programmable
3 programmable
EN61800-5-1
EN60068-2-6
Siemens BT300 HVAC Drive
Chapter 6 - Technical Information
Description
S [hydrogen sulfide] and SO
[sulfur dioxide]).
2
2
Technical Data
173 | 180
DPD01809
2016-06-07

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents