Logic
Selection Name
1
CS1: Forward (edge)
CS2: Inverted stop
1
Control signal (CS) 1 activates causing the
output frequency to rise. The motor runs
forward.
2
CS2 inactivates causing the frequency to drop
to 0.
3
CS1 activates causing the output frequency to
rise again. The motor runs forward.
4
Run enable signal is set to FALSE, which
drops the frequency to 0. The run enable
signal is configured with Run Enable
(P3.5.1.10).
5
Start attempt with CS1 is not successful
because Run enable signal is still FALSE.
Siemens Industry, Inc.
Building Technologies
Figure 13: I/O A Start/Stop logic = 1.
Table 22: Legend to IO A Start/Stop logic = 1.
Siemens BT300 HVAC Drive
Chapter 4 - Parameters and Menu Structure
Note
6
CS1 activates and the motor accelerates
(FWD) towards the set frequency because
the Run enable signal has been set to TRUE.
7
Keypad stop button is pressed and the
frequency fed to the motor drops to 0. (This
signal only works if KeypadStopButton
[P3.2.3] = Yes)
8
CS1 activates causing the output frequency
to rise again. The motor runs forward.
9
CS2 inactivates causing the frequency to
drop to 0.
Parameters (M3)
43 | 180
DPD01809
2016-06-07