Chapter 4 - Parameters and Menu Structure
Parameters (M3)
Structure
Parameter
P3.5.2.9
AI2 Signal Range
P3.5.2.10
AI2 Cutom Min
P3.5.2.11
AI2 Custom Max
P3.5.2.12
AI2 Signal Inv
P3.5.2.13
AI3 Signal Sel
P3.5.2.14
AI3 Filter Time
P3.5.2.15
AI3 Signal Range
P3.5.2.16
AI3 Cutom Min
P3.5.2.17
AI3 Custom Max
P3.5.2.18
AI3 Signal Inv
P3.5.2.19
AI4 Signal Sel
P3.5.2.20
AI4 Filter Time
58 | 180
Siemens Industry, Inc.
Building Technologies
Unit
Min
Max
0-10V/0-
2-10V/4-
20mA
20mA
%
-160
160
&
-160
160
Normal
Inverted
s
0
300
0-10V/0-
2-10V/4-
20mA
20mA
%
-160
160
&
-160
160
Normal
Inverted
s
0
300
Siemens BT300 HVAC Drive
Default
ID
0-10V/0-
390
Defines the signal range for the
20mA
analog input defined by AI2 Signal
Sel (P3.5.2.7). Ranges are as
follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc / 4..20 mA
NOTE: This setting can be
bypassed by using AI2 Custom Min
(P3.5.2.10) and AI2 Custom Max
(P3.5.2.11).
0
391
Defines the custom minimum to be
used for bypassing the AI2 Signal
Range (P3.5.2.9).
100
392
Defines the custom maximum to be
used for bypassing the AI2 Signal
Range (P3.5.2.9).
Normal
398
Defines the operation of the analog
input 2 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%, 10V
or 20 mA = 0%
AnIN Slot0.1 141
Defines the location of the signal to
be used as analog input 3.
1
142
Defines the time it takes to reach
63% of a step change in the analog
input signal defined by AI3 Signal
Sel (P3.5.2.13).
0-10V/
143
Defines the signal P3.5.2.13).
0-20 mA
Ranges are as follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI3 Custom Min
(P3.5.2.16) and AI3 Custom Max
(P3.5.2.17).
0
144
Defines the custom minimum to be
used for bypassing the AI3 Signal
Range (P3.5.2.15).
100
145
Defines the custom maximum to be
used for bypassing the AI3 Signal
Range (P3.5.2.15).
Normal
151
Defines the operation of the analog
input 3 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%, 10V
or 20m A = 0%
AnIN Slot0.1 152
Defines the location of the signal to
be used as analog input 4.
1
153
Defines the time it takes to reach
63% of a step change in the analog
input signal defined by AI4 Signal
Sel (P3.5.2.19).
Description
DPD01809
2016-06-07