Stopped Error Codes
Table IO lists stopped error codes for your controllers. These codes may be read
using the Modsoft " PC & I/O status" screen.
Table 10
Stopped Error Codes
Machine Stop Bits
Description
Ox7FFF
Controller unhealthy
0x8000
Controller stopped
0x4000
Bad I/O traffic cop. Mismatch
0x2000
PC in dim awareness
0x1000
Bad port intervention
0x0800
Bad segment scheduler
0x0400
Son did not start segment
0x0200
Bad power-down checksum (RAM Error)
0x0100
No EOL detected; Bad Network
0x0080
Watchdog expired
0x0040
Real time clock failed
0x0020
Bad coil used table
0x0010
Remote IO option failed
0x0008
Illegal node type user
0x0004
User logic checksum error
0x0002
Discretes disable error
0x000 1
Bad configuration
Note: These errors can be seen in combination. Use the Modsoft PC & l/O Status
screens to determine bit structure.
Figure 36 gives Modbus cable pinouts for use in troubleshooting or should you
need to fabricate your own.