Table 5 Port 1 Configuration
685El785El785Dl785K
685l785 ONLY
MEM
DIP
DIP/
DIPSW8
Port 1 Communication Parameters Taken from
Configuration Table
Port 1 Communication Parameters are:
RTU, 9600 BAUD, Even Parity, 1 Stop Bit
Address is set on Dip Switch underneath
if 6&X%5.
Port
1 Communication Parameters are:
RTU, 2400 BAUD, Even Parity, 1 Stop Bit
Address is set on Dip Switch underneath
if 68W85.
Bridge Mode capable only
if Panel programmed this
option (Default is NO Bridge
Mode)
Bridge Mode capable
without panel intervention
(i.e. automatic)
Bridge Mode capable
without panel intervention
(i.e. automatic)
The second Modbus Port on the 68.51785 is configurable only by using your pro-
gramming panel.
Modbus Port Software Configuration
You can use Modicon Modsoft programming panel software to set an internal
memory variable for either Modbus port 1 or port 2 (when the MEM/DIP slide
switch is in MEM).
Refer to Figure 11. The two settings available are:
RTU, 9600 baud, Even Parity,
1
Stop bit, (switch 8 in the position shown in
Figure 17) or, ASCII, 2400 baud, Even Parity,
1
Stop bit, (switch 8 position
" down" ).
w
Note
When the MEM/DIP enable slide is returned to MEM position,
Port
1
comm parameters and link address return to original memory
configured values after a power cycle.
38
System Planning
Gh4-0984-EDK