Output to I/O Service
38x Current*
Vl 5Vdc I/O
3.5A max
V2 4.3Vdc I/O3.5A max
48x Current*
Vl 5Vdc I/O
3.5A max
V2 4.3Vdc 1/03.5A max
V3-5Vdc I/O 0.250A max
*
When added, any combination of Vl and V2 must not exceed 3.5 Amperes
6axnax Current*
Vl 5Vdc CPU 1 .OA max
V2 5Vdc System Options & I/O 7.OA max
V3 4.3Vdc I/O 6.OA max
V4-5Vdc I/O 0.5A max
*
The combination of 2,3 and 4 cannot exceed 7.0 Amperes.
External Power Requirements
AC Isolation
Transformer
I oow (38x/48x)
0.5kVA (6axnax)
Ext 24Vdc P.S.
31W nom, @ 24Vdc (38x/48x) (24A peak); or
70W nominal (68x/78x) (24A peak)
RI/OHead Load
1.6A
max Q 5VDC
I/O Module Loads
See the Modicon Programmable Controller Systems
Manual (GM-098~SYS)
or the data sheet shipped
with your module.