Section 2
REF601/REJ601 overview
2.3
2.3.1
2.3.2
8
Operation Functionality
Relay functions
REF601/REJ601 offers pre-configured functionality which facilitates easy and fast
commissioning of switchgear. To emphasize the simplicity of relay's usage, only
application specific parameters needs to set within the relay's intended area of
application.
The settings can be changed via LHMI (Local Human-Machine Interface) or
through optional communication interface MODBUS master with setting
capability.
The relay offers protection, control, measurement and condition monitoring
functionality.
The table indicates the Functions supported by the IED
Table 1:
Relay functions
Function
Protection
Non Directional Over-current, Low set
Non Directional Over-current, High set
Non Directional Over-current, Instantaneous set
Non Directional Earth-fault, Low-set
Non Directional Earth-fault, High-set
3-phase Transformer Inrush detector
Control
1)
Circuit-breaker control
Condition monitoring
Trip circuit supervision
Measurement
Three-phase current measurement
Residual current measurement
1) Control functionality shall not be available in REJ601 relay
Optional function
Communication on MODBUS RTU Protocol
1MDU07212-YN Rev. A
IEC 60617
ANSI
3I>
51
3I>>
50-1
3I>>>
50-2
I0>
51N
I0>>
50N
3I2f>
68
I <-> O CB
I <-> O CB
TCS
TCM
3I
3I
Io
In
REF601 / REJ601
Application Manual