Access Level - ABB REF601 Applications Manual

Feeder protection and control/feeder protection
Hide thumbs Also See for REF601:
Table of Contents

Advertisement

Section 5
Use of LHMI
5.2.8.3
5.2.9
40
Submenu – Functional test
Submenu functional test allows performing simulation of each protection function
by giving a test current to the selected protection function.
Test
Test
Hardware
Test
BO
Test
Functional
Figure 19: Functional test menu of relay REF601/REJ601

Access level

This menu provides the password change facility for the different access levels.
Only Admin can change the password of the other access levels. Activating edit
mode by pressing Enter and Cancel button together can change password. User can
then enter new password. Enter button must be pressed before timeout period after
changing the password. Password can be of six different combinations of the
navigation keys. Each navigation key has its unique ID (1..4) which will be
selected as password for the different access levels. Only two key combinations
can be used for password entry/selection.
Figure 20: Access level menu
:YYY
Functional Test
NO; YES
I>
:YYY
Functional Test
NO; YES
I>>
:YYY
Functional Test
NO; YES
I>>>
:YYY
Functional Test
NO; YES
I0>
:YYY
Functional Test
NO; YES
I0>>
:YYY
1MDU07212-YN Rev. A
REF601 / REJ601
Application Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rej601

Table of Contents