1MDU07212-YN Rev. A
4.9
REF601 / REJ601
Application Manual

Signal Diagram

The figure below schematically illustrates the analogue input, binary input / output
and LED indications.
Figure 4:
Signal diagram of relay REF601/REJ601
Table 13:
Analog inputs
L1, L2, L3
Current transformer input for phase L1, L2, L3 , either 1A or 5A
according to order type.
Io
Earth current input through CBCT for external earth measurement,
either 1A or 5A according to order type.
Table 14:
Binary inputs
BI1
Default configured as UNBLOCK
BI2
Default configured as TCS
BI3
Default configured as external trip command to breaker
BI4
Default configured as reset command for resetting indications and
contacts
Protection and Control Function
Section 4
21