1MDU07212-YN Rev. A
6.4
6.5
REF601 / REJ601
Application Manual
Relay wiring
The connection wiring to the relay should be made by using single strand wire or
stranded wire with the use of insulated crimp terminal to maintain the insulation
requirements. The wire with below indicated cross-section should be used for
wiring:
0.2 - 2.5 sq. mm single-core
0.2 - 2.5 sq. mm finely stranded
Relay mounting and dimensions
All the mounting elements are integrated in the relay. The relay has been equipped
with in-build press fit mechanism.
The space requirement of mounting:
Overall dimensions (H x W x D)
Cutout dimensions (H x W)
Depth behind the panel
Weight
Figure 22: Overall mounting dimension of REF601/REJ601
: 160 x 130 x 151.1 mm
: 152 ± 0.5 x 122 ± 0.5 mm
: 148.5 mm
: 1.43 kg
Section 6
Installation
43