1MDU07212-YN Rev. A
3. Circuit Breaker Command: Binary inputs BI2 to BI4 can be configured to provide
4. Reset: Binary input BI2 to BI4 can be configured for reset operation. When the
5. Trip Circuit Supervision: Binary input BI2 is used to receive the invalidity of trip
All binary inputs BI1 to BI4 also support Inverted (I) operation.
4.7
4.8
REF601 / REJ601
Application Manual
external (remote) breaker open or breaker close command.
For routing circuit breaker opening or closing command from binary
input, it is necessary that user also configures binary output to receive
respective command.
rising edge is detected, the IED resets all the protection and control functions (all
internal timers are reset). It also resets the Start, Trip, Trip Ip, Trip Io and TCS fault
LEDs and de-latches the binary output.
circuit. No other binary input can be used for this purpose.

Breaker control and Trip command operation

Relay supports breaker control operation. The control operation can be done from
control push-buttons provided on relay front, from remote via MODBUS
communication or from signals wired to relay binary inputs duly configured for
control operation.

Trip Circuit Supervision

Application
The Trip Circuit Supervision TCS detects faults in the electrical trip / open control
circuit (which includes trip coil, trip contact, wiring and auxiliary voltage) of
circuit. It can supervise trip circuit in breaker open as well as breaker close
condition.
It is possible to enable/disable TCS functionality through configuration parameter.
For the TCS functionality the BI2 need to be connected in parallel to the trip output
BO2 as shown in the figure below. Additional the BI2 need to be configured for the
TCS functionally.