Installing The Air Plenum Kit In An Etsi Two-Post To Four-Post Rack - Cisco ASR 9001 Hardware Installation Manual

Hide thumbs Also See for ASR 9001:
Table of Contents

Advertisement

Unpacking and Installing the Chassis

Installing the Air Plenum Kit in an ETSI Two-Post to Four-Post Rack

Note
The air plenum kit is assembled and mounted in the rack before the Cisco ASR 9001 Router is installed.
To install the air plenum kit in an ETSI four-post open rack, follow these steps:
Procedure
Step 1
Place the plenum base on a flat and stable surface. Secure the left and right adapter plates to the front of the
plenum base using two Cisco supplied M5x10mm screws rack-mounting screws in the top and bottom screw
holes on the plenum base.
Step 2
Attach the left and right air baffles to the plenum base using the Cisco supplied M5x10mm screws (four for
each air baffle). The keyholes on each side of the plenum base will help to guide the air baffles into position
(see the figure below).
Cisco ASR 9001 and Cisco ASR 9001-S Routers Hardware Installation Guide
Installing the Air Plenum Kit
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Asr 9001-s

Table of Contents