For the transmission of the 4-20 mA signal, a two-pole M16 cable connector can be connected at position (1) at the
evaluation unit.
CAUTION!
The 4....20 mA interface is designed as an active current source and is galvanically separated
from the rest of the circuit by a 1 kV isolation barrier. The current to be measured depends on the
connected load.
Only a passive current sink is to be connected to the 4....20 mA interface. For correct
functioning, the connected load must lie within a range between 0 and max. 500 Ohm.
METPOINT
®
OCV
Cable connector with screen ring
Two-pole
M 16
Cable bushing 4-6 mm
Available as accessories.
Order number 4014143
Operation
61