Environmental Type Tests - Siemens RUGGEDCOM RS900GP Installation Manual

Hide thumbs Also See for RUGGEDCOM RS900GP:
Table of Contents

Advertisement

RUGGEDCOM RS900GP
Installation Guide
ESD
Radiated RFI
Fast Transient
Oscillatory
HV Impulse
Dielectric Strength

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60255-21-1
IEC 60255-21-2
EMI and Environmental Type Tests
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power Ports
Earth Ground Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Description
Cold Temperature
Dry Heat
Vibration
Shock
2.2 kV common and differential mode @ 1 MHz
Test Levels
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
2g @ 10-150 Hz
30g @ 11 ms
Test Levels
± 8 kV
± 15 kV
35 V/m
± 2 kV @ 2.5 kHz
± 1.5 kV
± 2 kV
2.2 kV common mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
2 kV (Failsafe Relay)
2 kV
Severity Levels
Class 2
Class 2