Figure 3: IRIG-B Simplified Circuit Schematic
1. Source
2. Cabling
The maximum number of devices (N) that can be connected to the source is determined by checking if the source
current (IS) required to drive the connected devices is less than the maximum drive current the source can
provide, and verifying that the load voltage (VL) the connected devices see is greater than the minimum required
voltage.
Section 1.3.3

IEEE 1588 Support

RSG2488 supports various IEEE 1588 time synchronization capabilities and provides synchronization in 1-step
and 2-step modes. However, of the 28 ports available, ports 2/4, 4/4, 6/4 and 7/2 only support 1-step mode and
select clock types. All other ports support both modes and all clock types.
1-Step Peer-to-Peer Transparent Clock
End-to-End Transparent Clock
End-to-End Slave Clock
End-to-End Master Clock
Peer-to-Peer Slave Clock
Peer-to-Peer Master Clock
Peer-to-Peer Ordinary/Transparent Clock
Boundary Clock
IEEE 1588 Support