SMC Networks ZSE30 Series Manual page 28

High-precision 2-color display digital pressure switch
Table of Contents

Advertisement

High-Precision Digital Pressure Switch
C
NPN (1 output) + Analog voltage output
Max. 28 V, 80 mA
Residual voltage 1 V or less
Analog voltage output
Output impedance: Approx. 1 kΩ
D
NPN (1 output) + Analog current output
Max. 28 V, 80 mA
Residual voltage 1 V or less
Analog current output
Max. load impedance:
Power supply voltage 12 V: 300 Ω
Power supply voltage 24 V: 600 Ω
Min. load impedance: 50 Ω
∗ The FUNC terminal is connected using a dedicated lead wire (ZS-38-5L or ZS-38-U) when the copy function is used. (Refer to "Copy function" on page 10.)
2-Color Display
Brown DC (+)
Load
Black OUT1
+
White OUT2
12 to
24 VDC
Load
FUNC
Blue DC (–)
Brown DC (+)
Load
Black OUT1
+
White OUT2
12 to
24 VDC
Load
FUNC
Blue DC (–)
ZSE30A
Series
E
PNP (1 output) + Analog voltage output
FUNC
Max. 80 mA
Residual voltage 1 V or less
Analog voltage output
Output impedance: Approx. 1 kΩ
F
PNP (1 output) + Analog current output
FUNC
Max. 80 mA
Residual voltage 1 V or less
Analog current output
Max. load impedance:
Power supply voltage 12 V: 300 Ω
Power supply voltage 24 V: 600 Ω
Min. load impedance: 50 Ω
(
)
F
/ISE30A
Brown DC (+)
Black OUT1
+
White OUT2
12 to
24 VDC
Load
Load
Blue DC (–)
Brown DC (+)
Black OUT1
+
12 to
White OUT2
24 VDC
Load
Load
Blue DC (–)
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ise30 series

Table of Contents