Table 3-4 Specifications - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Rated Output kVA
Rated Output kW
AC INPUT
Configuration
Voltage
Frequency
Reflected Current THDi
STATIC BYPASS INPUT
Configuration
Voltage
Frequency
BATTERY
Type
Ride Through
Nominal Voltage
Minimum Voltage
Number of Cells
AC OUTPUT
Configuration
Voltage
Voltage Regulation
Frequency
Frequency Regulation
Power Factor
Power Factor Range
Voltage THD
Transient Response
Transient Recovery Time
Voltage Unbalance
Phase Displacement
Inverter Overload
Bypass Overload
ENVIRONMENTAL**
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Paint Color
Clearance Required
Enclosure
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
Table 3–4 Specifications
100
90
3 phase, 3 wire
480 V (+15% to -20%)
60 Hz ±10%
3% typ. at 100% load (no input filter required)
3 phase, 3 wire
480 V ±10%
60 Hz ±5%
Lead Acid
Application Specific
480 Vdc
400 Vdc
240
3 phase, 3 wire
480 V
±1%
60 Hz
±0.01% in free running mode
0.9 nominal (0.9 Lagging to 1.0 within output kW rating)
0.9 to 1.0 Lagging (within output kW rating)
< 2% maximum THD at 100% linear load
< 5% maximum THD at 100% non-linear load
±2% maximum at 100% load step
±1% maximum at loss/return of AC power
±5% maximum at load transfer to/from static bypass
Less than 20ms
1% maximum at 100% unbalanced load
±1° maximum at 100% Load
125% for 2 minutes; 150% for 60 seconds
(with bypass available)
1000% for 1 cycle
Forced Air
32 °F to 104 °F (0 °C to 40 °C).
Recommended : 68゚F to 86゚F ( 20 °C to 30 °C)
5% – 95% Non-Condensing
0 to 7400 ft. (2255 m) No Derating at 40゚C
Indoor (free from corrosive gases and dust)
Munsell N1.5 (Black)
Top : 19.7 in. (500 mm)
Front : 39.4 in. (1000 mm)
Rear : 0 in. (0 mm)
Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if no sidecars used.
NEMA 1
160
225
144
202.5
15