Toshiba G9000 SERIES Installation And Operation Manual page 68

480/480 v 100/160/225 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Note 3
Code
Status
indication
message
UF109
DC UNBALANCED
ZERO PHASE
UF110
OVERCURRENT
UPS CONTROL
UF111
CIRCUIT ERROR
DC CIRCUIT
UF112
ABNORMAL
UF119
DC GROUND FAULT
CONTROL POWER
UF128
SUPPLY ABNORMAL
DC VOLTAGE
UF151
ABNORMAL
DC VOLTAGE
UF152
ABNORMAL
UF154
CB2 ABNORMAL
CHG.STOPPED
UF156
(BATTERY
OVERTEMP.)
BATTERY
UF157
OVERTEMPERA-
TURE
BATTERY LIQUID
UF158
LOW
UF159
DC GROUND FAULT
UPS CONTROL
UF160
CIRCUIT ERROR
CHG.STOPPED(DC
UF161
VOLT. ABNORMAL)
BATTERY
UF162
ABNORMAL
BATTERY VOLTAGE
UF163
ABNORMAL
VDB SENSOR
UF170
ABNORMAL
UPS CONTROL
UF171
CIRCUIT ERROR
CHG. STOPPED
UF172
(DEVICE STATUS)
58
Table 7–1 Fault Codes (Cont.)
Meaning
Major unbalance of the neutral point voltage.
Detection of converter zero-sequence
overcurrent.
Battery current unbalance.
Sudden change of the DC voltage level.
Detection of DC ground fault UF159 exceeds
10 seconds. UPS transfers to bypass.
Power supply voltage to IGBT driver PCB is
below the specified level.
24 hours after input power restoration,
batteries does not reach float voltage level.
Unable to equalize the voltage of various
batteries after 24 hours.
During UVR, status signal from CB2 is ON.
UF157 failure persisted for over 2 hours.
Detection of over temperature at the batteries.
Low level of battery electrolyte solution.
Detection of DC ground fault. Chopper
operation is stopped.
Abnormal behavior of DC current sensor.
UF151 failure is running for over 24 hours.
Failure detection based on battery self-check.
Battery voltage is abnormal.
Detection of a large variation of the difference
between control-only and protection-only
battery voltage.
Poor shared current in parallel chopper circuit;
or improper charging current.
Energy storage device error.
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
Guidance
Buzzer
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuousso
ENGINEER
und
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Continuous
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
Intermittent
CHECK BATTERY
sound
Intermittent
CHECK BATTERY
sound
Intermittent
CHECK BATTERY
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
CALL SERVICE
Intermittent
ENGINEER
sound
Note 1
Note 2
External
Failure
relay contact
lamp
Major
Lit on
Major
Lit on
Major
Lit on
Major
Lit on
Major
Lit on
Major
Lit on
Minor
Flicker
Minor
Flicker
Minor
Flicker
Minor
Flicker
Battery abnormal
Minor
Flicker
Battery abnormal
Minor
Flicker
Battery abnormal
Minor
Flicker
Minor
Flicker
Minor
Flicker
Minor
Flicker
Minor
Flicker
Minor
Flicker
Minor
Flicker
Minor
Flicker