Toshiba G9000 SERIES Installation And Operation Manual page 74

480/480 v 100/160/225 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Installation Planning Guide for 160kVA UPS
Dimensions
(W x D x H)
Inches
27.6" x 32.8" x 80.6"*
* Height includes removable fan housing – Frame height is 78.7."
** 0" clearance for peripheral equipment, 1" clearance for walls.
Maximum Input Power Demand
Normal Mode (Recharge Mode)
kVA
PF
151 (170)
>0.99
Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power
Demand
kVA
PF
Amps
160
0.9
192
Battery Capacity Required
Maximum Discharge
for Full Load Output
kWB
149 @ 0.9 PF
Rated Output Power
kVA
PF
Amps
160
0.9
192
mportant Notes:
I
1.
Maximum input current is limited to 111% of the full-load
input current.
2.
Output load conductors are to be installed in separate
conduit from input conductors.
3.
Control wires and power wires are to be installed in
separate conduits.
4.
Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
5.
Wiring shall comply with all applicable national and local
electrical codes.
6.
Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 3-wire + ground.
- Alternate AC Input: 3φ, 3-wire + ground.
- AC Output: 3φ, 3-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7.
Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
8.
Maximum battery discharge current based on lowest
permissible discharge voltage of 1.67 VPC.
9.
DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
64
Standard System: 480V Input, 480V Output
General Mechanical Information
Approximate Full-Load
Floor
Weight
Heat Rejection
Loading
2
Lbs.
Lbs./ft.
kBtu/Hr
860
137
18.3
Primary AC Input (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
181 (204)
250 AT
Suggested External
Overcurrent Protection
Amps
250 AT
Battery Input (480VDC Nominal)
Suggested External
at Full Load Output
Overcurrent Protection
Amps DC
Amps
372
400 AT
AC Output (480V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
250 AT
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
Mechanical Clearance (Inches)from UPS
for Ventilation and Maintenance Access
Top
Front
20"
40"
External Feeder Wire Size: Min. – Max. Per Phase
Amps
AWG or kcmil at 75º C Temp. Rating
250 kcmil – 300 kcmil
External Feeder Wire Size:
Min. – Max. Per Phase
AWG or kcmil at 75º C Temp. Rating
250 kcmil – 300 kcmil
External Feeder Wire Size: Min.
AWG or kcmil at 75º C Temp. Rating
(2) x 3/0 – (2) x 250 kcmil
External Feeder Wire Size:
Min. – Max. Per Phase //
AWG or kcmil at 75º C Temp. Rating
250 kcmil – 300 kcmil
10. Weights do not include batteries or other auxiliary equipment
external to the UPS.
11. Cable sizing calculations based on the following assumptions:
- Minimum size is smallest size based on ampacity at 30 °C.
- Maximum size cable is based on cable bend radius
limitations at the UPS terminals.
- Not more than 3 current-carrying conductors installed in
conduit in ambient temperature of 30 °C.
- Temperature rating of copper conductors/terminals: 75 °C.
- Reference: 2005 NEC Handbook, Table 310.16.
NOTE: Consult latest edition of applicable national and
local codes for possible variations.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
TOSHIBA INTERNATIONAL CORPORATION
Social Infrastructure Systems Group
Power Electronics Division
13131 West Little York Road
Houston, TX 77041
Telephone: (800) 231-1412
Fax: (713) 896-5212
Web Site: www.toshiba.com/tic
Bottom
Sides**
Back
0"
0"
0"
Max.