Figure 5-9 Automatic Startup Of Inverter And Converter; Figure 5-10 Close Battery Breaker - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

f.) FOR GUIDANCE IN STARTING THE UPS, select "OPERATION" tab on the LCD panel, then press
the "STARTUP GUIDANCE" icon (Figure 4-3) and follow the on-screen directions to continue UPS
start-up (Figure 4-4). (The directions are the same as given in the following steps.)
OR remain on the "MAIN" tab and continue with step g)..
!
When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start
operation can only be performed remotely. If local inverter start operation is required (at the UPS),
select "LOCAL ONLY" or "REMOTE & LOCAL" in the OPERATION MENU.
NOTE
a.
g)
Close the Battery Breaker. (The START/STOP icon will not work until the battery breaker is closed.)
The display will show CB2 is closed and the battery backup is now online. (Figure 5-10)
h)
Press the STOP/START icon on the display, then press and hold the START button (Figure 5-11a) for two
(2) seconds until the UPS transfers to load on INV. (Figure 5-11b)
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004

Figure 5-9 Automatic Startup of Inverter and Converter

Figure 5-10 Close Battery Breaker

b.
47

Advertisement

Table of Contents
loading

Table of Contents