Table 2-2 Rating Of Bypass Input Circuit Breaker - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

!
NOTE
This UPS does not include a Bypass input circuit breaker (MCCB) to protect the
bypass circuit. The Bypass input circuit breaker (MCCB) is to be field supplied and
installed. Recommended Breaker (MCCB)'s Specifications are as follows:
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
100
160
225
AC input and AC output overcurrent protection and disconnect devices shall be field supplied and
installed. The DC circuit breaker (MCCB) shall be field supplied and installed.
The overcurrent protection device should be installed in the Battery cabinet and rated as indicated
in Table 3–7.
Note: The DC input overcurrent protection (Battery disconnect breaker) hereinafter will be referred
as "CB2".
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
WARNING 4
Table 2–2 Rating of Bypass Input Circuit Breaker
480
480
480
Breaker (A)
120
150
192
250
271
350