Table 4-1 External Input Functions - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

The available programmable Input parameters are detailed in
Code
Function
0
NONE
1 *
REMOTE START
2 *
REMOTE STOP
3
POWER DEMAND 1
4 *
POWER DEMAND 2
5
BATTERY LIQUID LOW
6 *
BATTERY TEMP
ABNORMAL
7
GENERATOR RUN
8
ASYNCHRONOUS
9
ANOTHER BUS SYNC
10
REMOTE INVERTER (MMS) Starts all UPS inverters in an MMS system from a remote location.
11
REMOTE BYPASS (MMS)
12
EXT.BYP dV STR
13
USE IB LIMIT 2
14
CHARGER STOP
15
EXTERNAL ALARM
16
CB2 EX
17
CHARGE DEVICE ERR
18
CB1 ON IL
31
TRACE TRIGGER
*Default Settings from Factory.
28
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
Table 4–1 External Input Functions
Starts UPS inverter from remote location. Use momentary (0.5 to 4 sec.)
switches only. This is the default setting on IN1
Stops UPS inverter from remote location. Use momentary (0.5 to 4 sec.)
switches only. This is the default setting on IN2
Driven by any customer-provided NO (Normally Open) dry contact. Closing
the contact limits the input current to a value (10-150% of the UPS's rated
input) set in the TEST MENU – "Power Demand Level 1" by an Authorized
Toshiba Service Provider. Opening the contact returns the UPS to its normal
operation parameters.
This is the default setting on IN4.
Driven by any customer-provided NO (Normally Open) dry contact. Closing
the contact limits the input current to a value (10-150% of the UPS's rated
input) set in the TEST MENU – "Power Demand Level 2" by an Authorized
Toshiba Service Provider. Opening the contact returns the UPS to its normal
operation parameters.
Annunciates "UF158 BATTERY LIQUID LOW", and is used with an electrolyte
level sensor in a wet cell battery system.
Driven by any customer-provided NO (Normally Open) dry contact thermal
detection device installed in the UPS's Battery Cabinet(s). When the contact
closes, the UPS decreases its battery charging maximum limit to 95% of the
set charging voltage. If the contacts stay closed (the battery temp is still
abnormal) for two hours, the UPS will shut off its battery charger. (Battery
operation will still possible)
Inhibits transfer to bypass.
Inverter operates in free rum mode. (In other words, inverter does not track
bypass as sync source.)
Inverter will sync to an external source. For use with External Sync
packages.
Stops all UPS inverters in an MMS system from a remote location.
Inverter voltage is adjusted to match bypass voltage.
Use battery charge rate 2. This level is set in the TEST MENU by an
Authorized Toshiba Service Provider.
Battery charger will be stopped.
Annunciates "UA890 EXTERNAL ALARM".
Provides for another aux battery breaker (CB2) contact, similar in function to
the standard battery aux contact.
Energy storage device error signal. Mainly used with flywheels to annunciate
recharge fault.
Stops the rectifier converter remotely.
For use with the internal wave capture tool; for use by Authorized Toshiba
Service Providers.
.
Table 4–1
Description
This is the default setting on IN3