Table 8-1 Fault Codes - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 100/160/225 kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Note 3
Code
Status message
indication
AC INPUT VOLTAGE
UA801
OUT OF RANGE
AC INPUT
UA802
FREQUENCY OUT OF
RANGE
AC INPUT PHASE
UA803
ROTATION ERROR
CONVERTER OPE.
UA804
PROHIBITED
INVERTER
UA805
OVERLOAD
INVERTER
UA806
OVERLOAD
INVERTER
UA807
OVERLOAD
INVERTER
UA808
OVERLOAD
INVERTER
UA810
OVERLOAD
BYPASS VOLTAGE
UA812
OUT OF RANGE
BYPASS PHASE
UA813
ROTATION ERROR
BYPASS
UA814
FREQUENCY OUT OF
RANGE
TRANSFER
UA815
PROHIBITED
EMERGENCY STOP
UA817
ACTIVATED
TRANSFER
UA821
PROHIBITED
TRANSFER
UA822
PROHIBITED
56
Table 8–1 Fault Codes
Meaning
Input line voltage is out of the specified range.
Input line frequency is out of the specified
range.
Input line power conductors are not wired in a
proper phase sequence.
The converter interlock is active.
The output load current has exceeded 105% of
the rated current.
The output load current has exceeded 110% of
the rated current.
The output load current has exceeded 125% of
the rated current.
The output load current has exceeded 150% of
the rated current.
Short time over-current has been detected
during the inverter operation.
Bypass line voltage is out of the specified
range.
Bypass line power conductors are not wired in
a proper phase sequence.
Bypass line frequency is out of the specified
range.
Transfer to the bypass is not available due to
bypass abnormality.
The emergency stop was activated by the
EPO switch or an external contact.
The UPS could not transfer to the bypass
because the inverter output was not
synchronized to the bypass.
The UPS could not transfer to the bypass
because external "generator operation" signal
indicates a backup generator is in operation.
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
Guidance
Buzzer
CHECK INPUT
Intermittent
POWER SOURCE
sound
CHECK INPUT
Intermittent
POWER SOURCE
sound
CHECK INPUT
Intermittent
POWER SOURCE
sound
Intermittent
sound
WARNING :
Intermittent
DECREASE
sound
LOAD
WARNING :
Intermittent
DECREASE
sound
LOAD
WARNING :
Intermittent
DECREASE
sound
LOAD
WARNING :
Intermittent
DECREASE
sound
LOAD
WARNING :
Intermittent
DECREASE
sound
LOAD
CHECK BYPASS
Intermittent
INPUT
sound
CHECK BYPASS
Intermittent
INPUT
sound
CHECK BYPASS
Intermittent
INPUT
sound
Intermittent
sound
Note 1
Note 2
External
Failure
relay contact
lamp
Alarm
AC input abnormal
Alarm
AC input abnormal
Alarm
AC input abnormal
Alarm
Alarm
Overload
Alarm
Overload
Alarm
Overload
Alarm
Overload
Alarm
Overload
Alarm
Bypass input
abnormal
Alarm
Bypass input
abnormal
Alarm
Bypass input
abnormal
Alarm
Alarm
Alarm
Alarm