D) External Battery Supply
Please refer to the following when installing and maintaining batteries:
1. The customer shall refer to the battery manufacturer's installation manual for
!
battery installation and maintenance instructions.
2. The maximum permitted fault current from the remote battery supply, and the DC
voltage rating of the battery supply over-current protective device are shown in
NOTE
Table 5–3.
UPS Capacity
(kVA)
100
160
225
5.3

PROCEDURE FOR CABLE CONNECTIONS

1.
Confirm the capacity of the UPS being installed. Identify the input/output power
terminal blocks accordingly as shown in the Figure 5-1 and Figure 5-2.
2.
Connect the internal control wire and power wire.
(1) Control wire Inter-connect
1.
CB2 UVR to terminal TN1-1, 2 of external I/F PCB IOAU-09.
2.
CB2 ON Auxiliary to terminal TN1-3, 4 of external I/F PCB IOAU-09.
(2) Power wire (AC input, Bypass input, AC output) Inter-connect
a.) From user's distribution panel
1. X1 (A-phase) to A bus bar in UPS
2. X2 (B-phase) to B bus bar in UPS
3. X3 (C-phase) to C bus bar in UPS
b.) DC Input to UPS
1.
Positive cable to BP bus bar in UPS
2.
Negative cable to BN bus bar in UPS
36
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
Table 5–3 Maximum Permitted Fault Current
DC Voltage
Rating (V)
480
480
480
Maximum Fault
Current Permitted (A)
25,000
25,000
25,000