11 Supplement
Connection cable
Sensor version
4 ... 20 mA/HART
Profibus PA, Founda-
tion Fieldbus
Integrated clock
Date format
Time format
Time zone Ex factory
Rate deviation max.
Additional output parameter - Electronics temperature
Output of the temperature values
Ʋ Analogue
Ʋ Digital
Range
Resolution
Accuracy
Voltage supply
Operating voltage
Ʋ Version for low voltage
Ʋ Version for mains voltage
Reverse voltage protection
Max. power consumption
Electrical protective measures
Protection rating
Overvoltage category (IEC 61010-1)
Ʋ Version with low voltage
Overvoltage category (IEC 61010-1) - Version with mains voltage
Ʋ up to 2000 m (6562 ft) above sea level III
Ʋ up to 5000 m (16404 ft) above sea
level
Ʋ up to 5000 m (16404 ft) above sea
level
Degree of soiling
Protection rating (IEC 61010-1)
74
Cable length
Standard cable
50 m
25 m
Four-wire
Configuration, connection cable
Special cable
●
–
Day.Month.Year
12 h/24 h
CET
10.5 min/year
Via the additional current output
Depending on the electronics version via the HART,
Profibus PA, Foundation Fieldbus or Modbus signal
-40 ... +85 °C (-40 ... +185 °F)
< 0.1 K
±3 K
9.6 ... 48 V DC, 20 ... 42 V AC, 50/60 Hz
90 ... 253 V AC, 50/60 Hz
Integrated
4 VA; 2.1 W
IP 66/IP 67 (NEMA 4X)
das speisende Netzteil kann an Netze der Überspan-
nungskategorie III angeschlossen werden
III - Only with connected overvoltage protection
II
3
I
VEGAPULS 67 • 4 ... 20 mA/HART - four-wire
Screened
–
–
●
●