Setup - Damping
Setup - Current output
mode
Setup - Current output
Min./Max.
VEGAPULS 67 • 4 ... 20 mA/HART - four-wire
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
5. Save settings with [OK]
To damp process-dependent measured value fluctuations, set an
integration time of 0 ... 999 s in this menu item.
Depending on the sensor type, the factory setting is 0 s or 1 s.
In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 ... 20 mA, failure mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.