Vega VEGAPULS 67 Operating Instructions Manual page 61

Radar sensor for continuous level measurement of bulk solids
Hide thumbs Also See for VEGAPULS 67:
Table of Contents

Advertisement

Code
Text message
F125
Impermissible electronics
temperature
F260
Error in the calibration
F261
Error in the instrument set-
tings
F264
Installation/Setup error
F265
Measurement function dis-
turbed
Function check
Code
Text message
C700
Simulation active
Out of specification
Code
Text message
S600
Impermissible electronics
temperature
VEGAPULS 67 • 4 ... 20 mA/HART - four-wire
Cause
– Temperature of the
electronics in the non-
specified range
– Error in the calibration
carried out in the factory
– Error in the EEPROM
– Error during setup
– False signal suppression
faulty
– Error when carrying out
a reset
– Adjustment not within
the vessel height/meas-
uring range
– Max. measuring range
of the instrument not
sufficient
– Sensor no longer carries
out a measurement
– Operating voltage too
low
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Cause
– A simulation is active
The following table shows the error codes and text messages in the
status message "Out of specification" and provides information on
causes as well as corrective measures.
Cause
– Temperature of the
electronics in the non-
specified range
9 Diagnosis, asset management and service
Rectification
– Check ambient tem-
perature
– Isolate electronics
– Use instrument with
higher temperature
range
– Exchanging the elec-
tronics
– Send instrument for
repair
– Repeat setup
– Carry out a reset
– Check or correct instal-
lation and/or parameter
adjustment
– Use an instrument with
bigger measuring range
– Check operating voltage
– Carry out a reset
– Disconnect operating
voltage briefly
Rectification
– Finish simulation
– Wait for the automatic
end after 60 mins.
Rectification
– Check ambient tem-
perature
– Isolate electronics
– Use instrument with
higher temperature
range
DevSpec State in CMD
48
Bit 7 of Byte 0...5
Bit 8 of Byte 0...5
Bit 9 of Byte 0...5
Bit 10 of Byte 0...5
Bit 11 of Byte 0...5
DevSpec State in CMD
48
"Simulation Active" in
"Standardized Status 0"
DevSpec State in CMD
48
Bit 5 of Byte 14...24
61