Vega VEGAPULS 67 Operating Instructions Manual page 18

Radar sensor for continuous level measurement of bulk solids
Hide thumbs Also See for VEGAPULS 67:
Table of Contents

Advertisement

4 Mounting
18
Fig. 10: Recommended socket mounting
If the medium has good reflective properties, VEGAPULS 67 can
also be mounted on a longer socket piece. Recommended values
for socket heights are specified in the following illustration. You must
carry out a false echo storage afterwards.
The below charts specify the max. pipe socket length h depending on
the diameter d.
Socket diameter d
80 mm
100 mm
150 mm
Socket diameter d
3"
4"
6"
Tip:
In new facilities it is useful to incline the vessel socket in the direction
of the outlet. False reflections from the vessel wall are thus reduced
and measurement all the way down to the bottom of the conical outlet
is possible.
d
Socket length h
≤ 300 mm
≤ 400 mm
≤ 500 mm
Socket length h
≤ 11.8 in
≤ 15.8 in
≤ 19.7 in