JUMO mTRON T Manual page 95

Measuring,control, and automation system
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

7.3.2
Modbus addresses for each multichannel controller module
NOTE!
Signals with labels "NV_..." are intended for the function that corresponds to the respective
default names. However, the function ultimately depends on how the signals are used in the
configuration.
Signals from the central processing unit to a multichannel controller module
Address
Hex.
Dec.
0x0002
2
0x0008
8
0x000A
10
0x000C
12
0x000E
14
0x0010
16
Data type/
Access Signal designation
bit number
Bit field 64
R/O
Float
R/O
Float
R/O
Float
R/O
Float
R/O
Float
R/O
7 Modbus address tables
0xFF; for setpoint changeover of controller channels 1 to 4
Bit 0: setpoint changeover of controller channel 1 bit 0
(NV_SP01Changeover1)
Bit 1: setpoint changeover of controller channel 1 bit 1
(NV_SP01Changeover2)
Bit 2: setpoint changeover of controller channel 2 bit 0
(NV_SP02Changeover1)
Bit 3: setpoint changeover of controller channel 2 bit 1
(NV_SP02Changeover2)
Bit 4: setpoint changeover of controller channel 3 bit 0
(NV_SP03_Changeover1)
Bit 5: setpoint changeover of controller channel 3 bit 1
(NV_SP03_Changeover2)
Bit 6: setpoint changeover of controller channel 4 bit 0
(NV_SP04_Changeover1)
Bit 7: setpoint changeover of controller channel 4 bit 1
(NV_SP04_Changeover2)
Bit 8 to 11 = 0xF00;
for parameter block switching of controller channel 1 to 4
(NV_C01ParamSet to NVC04ParamSet)
Bit 12 to 19 = 0xFF000 : free
Bit 20 to 23 = 0xF00000;
for manual mode on controller channel 1 to 4
(NV_C01ManualMode to NVC04ManualMode)
Bit 24 to 27 = 0xF0000000 : free
Bit 32 to 39 = 0xFF00000000;
for NV digital inputs 3 to 10 (NV_DO03 to NV_DO10)
Bit 40 to 48 = 0x1FF0000000000;
for signal suppression 1 to 8 (NV_SR01 to NV_SR08)
Actual value for controller channel 1 (NV_C01ActualValue)
Setpoint value for controller channel 1 (NV_C01Setpoint)
Actual value for controller channel 2 (NV_C02ActualValue)
Setpoint value for controller channel 2 (NV_C02Setpoint)
Actual value for controller channel 3 (NV_C03ActualValue)
95