7.3.5
Modbus addresses for each 12-channel digital input/output module
Process values from the central processing unit to the 12-channel digital input/output module
Address
Hex.
Dec.
0x0000
0
Process values from the 12-channel digital input/output module of the central processing unit
Address
Hex.
Dec.
0x0002
2
Data type/
Access Signal designation
bit number
Bit field 32
R/O
Data type/
Access Signal designation
bit number
Bit field 32
R/O
7 Modbus address tables
Bit 6 = 0x40: digital output 1
Bit 7 = 0x80: digital output 2
Bit 8 = 0x100: digital output 3
Bit 9 = 0x200: digital output 4
Bit 10 = 0x400: digital output 5
Bit 11 = 0x800: digital output 6
Bit 12 = 0x1000: digital output 7
Bit 13 = 0x2000: digital output 8
Bit 14 = 0x4000: digital output 9
Bit 15 = 0x8000: digital output 10
Bit 16 = 0x10000: digital output 11
Bit 17 = 0x20000: digital output 12
Bit 0 = 0x01: digital input 1
Bit 1 = 0x02: digital input 2
Bit 2 = 0x04: digital input 3
Bit 3 = 0x08: digital input 4
Bit 4 = 0x10: digital input 5
Bit 5 = 0x20: digital input 6
Bit 6 = 0x40: digital input 7
Bit 7 = 0x80: digital input 8
Bit 8 = 0x100: digital input 9
Bit 9 = 0x200: digital input 10
Bit 10 = 0x400: digital input 11
Bit 11 = 0x800: digital input 12
111