6.1.
Password Protection
iBoot-G2 uses two username/password credential sets, one for normal
power control (User) and one that also provides access to the setup
functions (Admin).
Default Credentials:
Role
Administrator
User
Open your browser and enter the IP address of iBoot-G2 into the
address bar. If you have changed the IP address by any of the methods described, enter that address,
otherwise, use the default IP address 192.168.1.254
Enter the username and password as prompted. When the proper username/password is received the
Control and Status Page is displayed.
6.2.
Control and Status Page
Once the user is validated, the Control and
Status is displayed. (Only one person can be
connected to the iBoot-G2 at a time.)
To control the power, click on the appropriate
button. During power cycling, the Power Status
bar will indicate the temporary status, with a
blue background. Once the cycle is complete,
the status bar will revert to its original condition.
To abort a power cycle, click on either Power
On or Power Off buttons. iBoot-G2 will assume
the status selected.
If the AutoPing features is in use, the page will
also display the current status, OK or Failed, for
each AutoPing used, with a counter of how
many times it failed and how many times the
Action was triggered.
Admin credentials, reset buttons for the Fail and
Trigger counters are provided.
Use the Refresh button to obtain the latest
status of iBoot. Using your browser's refresh
button can lead to inadvertent power switching.
If an NTP server is being used, the time of the
last refresh will be shown in the upper right
corner.
V110120E

6. Web Browser Operation

Username (fixed)
admin
user
If connecting with the
iBoot-G2
Password (user set)
admin
user
Enter Username and Password
iBoot-G2 Status Page
AutoPing Status
Logout Page