Temperature/Humidity; Cleanliness; Emi - HP HPE FlexFabric 5930 Installation Manual

Table of Contents

Advertisement

Temperature/humidity

Maintain appropriate temperature and humidity in the equipment room.
Lasting high relative humidity can cause poor insulation, electricity leakage, mechanical
property change of materials, and metal corrosion.
Lasting low relative humidity can cause washer contraction and ESD and cause problems
including loose screws and circuit failure.
High temperature can accelerate the aging of insulation materials and significantly lower the
reliability and lifespan of the switch.
For the temperature and humidity requirements of different switch models, see
views and technical

Cleanliness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of
metal components and contact points, especially when indoor relative humidity is low. In the worst
case, electrostatic adsorption can cause communication failure.
Table 2 Dust concentration limit in the equipment room
Substance
Dust
NOTE:
Dust diameter ≥ 5 μm
The equipment room must also meet limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in
Table 3 Harmful gas limits in the equipment room
Gas
SO
2
H
S
2
NH
3
Cl
2

EMI

All electromagnetic interference (EMI) sources, from outside or inside of the switch and application
system, adversely affect the switch in the following ways:
A conduction pattern of capacitance coupling.
Inductance coupling.
Electromagnetic wave radiation.
Common impedance (including the grounding system) coupling.
To prevent EMI, use the following guidelines:
If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE)
to filter interference from the power grid.
specifications."
Concentration limit (particles/m³)
4
≤ 3 x 10
(no visible dust on the tabletop over three days)
Table
3.
Maximum concentration (mg/m³)
0.2
0.006
0.05
0.01
3
"Appendix A Chassis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents