Commissioning

You carry out commissioning with the IOP using one of thebasic commissioning wizards
(Page 12). If the IOP does not contain the actual frequency converter software, a message is
displayed "Update is required". You can find the required data in the Internet under
(http://support.automation.siemens.com/WW/view/en/43896115).
In the basic commissioning select the control mode for the motor, enter the motor data and
define the function of the frequency converter interfaces. You can find the cabling diagrams
in Section Selecting the interface assignment (Page 21) .
When commissioning with an application wizard, you may have to supplement the wiring of
the terminal strip to meet the needs of the application.
Table 3- 1
Overview of the commissioning
● When commissioning with wizards, the first step is to RESET to the factory settings. This
● Before the frequency converter accepts your commissioning data, you must check these
● The last step is the prompt SAVE or INTERRUPT WIZARD? Select SAVE!
● You can subsequently change your frequency converter settings (Section The most
● Once you have completed commissioning, you should back up the settings of your
Frequency converters with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 01/2011, A5E02792536C AB
Motor data on the rating plate
D-91056 Erlangen
D-91056 Erlangen
3~Mot. 1LE10011AC434AA0
3~Mot. 1LE10011AC434AA0
IEC/EN 60034 100L
IEC/EN 60034 100L
IMB3
IMB3
IP55
IP55
25 kg
25 kg
Th.Cl. 155(F)
Th.Cl. 155(F)
-20°C
-20°C
Tamb
Tamb
UNIREX-N3
Bearing
Bearing
UNIREX-N3
DE
DE
6206-2ZC3
6206-2ZC3
15g
15g
Intervall: 4000hrs
Intervall: 4000hrs
NE
NE
6206-2ZC3
6206-2ZC3
11g
11g
60Hz:
60Hz:
SF 1.15 CONT
SF 1.15 CONT
V
Hz
A
kW
PF
400
50
3.5
1.5
0.73
690
Y
50
2.05
1.5
0.73
460
60
3.15
1.5
0.69
ensures that the frequency converter is in a defined basic setting.
After the basic commissioning, the wizard that you selected guides you through
application-specific settings.
and confirm them. You do this using the last but one menu item OVERVIEW OF THE
SETTINGS. In this screen, scroll down to CONTINUE and acknowledge it with OK.
Commissioning using the wizards has now been completed.
important parameters at a glance (Page 30).
frequency converter e.g. on the IOP, so that they are not lost if the frequency converter
develops a defect (Section Data backup on the memory card (Page 34)).
E0807/0496382_02 003
E0807/0496382_02 003
40°C
40°C
NEMA
NEMA
MG1-12
MG1-12
TEFC
TEFC
Design A
Design A
2.0 HP
2.0 HP
NOM.EFF
NOM.EFF
rpm
V
V
84.5%
84.5%
970
380 - 420
380 - 420
3.55-3.55
3.55-3.55
84.5%
84.5%
970
660 - 725
660 - 725
2.05-2.05
2.05-2.05
86.5%
86.5%
1175
1. Motor voltage = P0304
2. Motor frequency = P0310
3. Motor current = P0305
4. Motor power = P0307
5. Motor power factor = P0308
6. Rated motor speed = P0311
A
A
CL
CL
K
K
3
27