Commissioning

3.1 Settings in the basic commissioning menu

3.1
Settings in the basic commissioning menu
Start the menu: WIZARD / BASIC COMMISSIONING
The "Basic Commissioning" wizard guides you through commissioning in the following steps:
No.
Input screen of the IOP
01/21
Restore factory settings
02/21
Control mode
03/21
Encoder type
04/21
Encoder pulses
05/21
Motor data
06/21
Characteristic
07/21
Motor connections
08/21
Motor data
09/21
Rated power
10/21
Motor speed
11/21
Motor current
12/21
Motor voltage
13/21
Motor data ID
14/21
I/O configuration
15/21
Minimum speed
16/21
Ramp-up
17/21
Ramp-down
18/21
Overview of the settings
19/21
Save settings
20/21
Saving, please wait
21/21
Motor data ID
1) If the IOP Assistant does not offer this setting, after completing the basic commissioning, set parameter p1900 to a value
of 1 using the parameter menu.
28
Selected setting on the IOP
[1] yes
[0] V/f with linear characteristic
[0] Not activated
Encoder type not activated
P0408 is set as default
[0] Europe 50 Hz, kW
50 Hz / 87 Hz
Observe the motor connection (star / delta)!
Enter motor data for 50 Hz (refer to 06/23)
Enter [kW] (or [hp]) according to the motor rating plate
Enter [rpm] according to the motor rating plate
Enter [A] according to the motor rating plate
Enter [V] according to the motor rating plate
[1] Stationary and rotating measurement
If the motor cannot freely rotate, e.g. if travel is
mechanically limited, select the setting [2] "MotID only
stationary".
Select a pre-defined setting, see Section: Selecting the
interface assignment (Page 21)
Enter the minimum speed [rpm], above which the motor
should operate.
Time [s] in which the motor should accelerated from
standstill up to the maximum speed (P1082).
Time [s] in which the motor should be decelerated from
the maximum speed (P1082) down to standstill.
Check list + Select < Continue> + OK
Save
...
A motor data ID is started at the next ON command.
Frequency converters with Control Units CU230P-2; CU240B-2; CU240E-2
Confirm with OK
Select characteristic
Confirm with OK
Confirm with OK
1)
Confirm with OK
Confirm with OK
Confirm with OK
Getting Started, 01/2011, A5E02792536C AB
Parameter
P0970 = ...
P1300 = ...
P0400 = ...
P0100 = ...
P0307 =
P0311 =
P0305 =
P0304 =
P1900 = ...
P0015 = ...
P1080 = ...
P1120 = ...
P1121 = ...
P3900 = ...