Siemens SINAMICS BOP-2 Operating Instructions Manual page 31

Basic operator panel 2
Hide thumbs Also See for SINAMICS BOP-2:
Table of Contents

Advertisement

Table 3- 6
Motor data according to the rating plate
Parameter
Possible settings
p0100
Motor standard IEC / NEMA
0: Europe 50 [Hz]
p0300
Motor type selection
0: No motor
1: Induction motor
2: Synchronous motor
p0304
Motor voltage in [V]
p0305
Motor current in [A]
p0307
Motor frequency in [kW] or [hp]
p0310
Motor frequency in [Hz]
p0311
Motor speed in [rpm]
p0625
Ambient temperature of the motor in [°C]
p0640
Current limit of the motor in [A]
Changing the function of a terminal
Table 3- 7
Digital inputs
Parameter
Terminals
CU240B-2
p0722.0
5 / 69
p0722.1
6 / 69
p0722.2
7 / 69
p0722.3
8 / 69
p0722.4
-
p0722.5
-
Table 3- 8
Changing the function of a digital input
Changing the function
1. Select the required function marked using a "BI" parameter.
2. Set this parameter to the value of the status parameter
r0722.x of the required digital input.
Frequency converters with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 01/2011, A5E02792536C AB
Terminals
Terminals
CU240E-2
CU230P-2
5 / 69
5 / 69
6 / 69
6 / 69
7 / 69
7 / 69
8 / 34
8 / 69
9 / 34
9 / 69
10 / 34
10 / 69
3.3 The most important parameters at a glance
Signal
Command sources of important functions
DI 0
p0840 - ON/OFF (OFF1)
p2103 - acknowledge faults
DI 1
p1055/p1056 - jog mode
DI 2
p1035/p1036 - motorized potentiometer
DI 3
p1020 ... p1023 - fixed speed setpoint
p1230 - activate DC braking
DI 4
p2200 - enable technology controller
DI 5
Examples
Function
: Switch-on motor via DI 2.
Setting
: p0840 = 722.2
r0722.2
Function
: Acknowledge fault using DI 1.
Setting
: p3981 = 722.1
r0722.1
Commissioning
p0840
722.2
p2103
722.1
31