Section 5 - Procedures
5.3-3
LED Error Codes - Code Breakdown Chart
Diagnostic sequence dependant on LED flash code:
No Last Caldate
Load Not Calibrated
Height Not Calibration
An EZcal is required!
Waiting For Neutral
Drive/Lift Inputs Faulty!
Up/Down Select Inputs Active Together
EMS Inputs Faulty!
Check inputs on P2 pins 1,2,3,4,5,6,7,8.
P3-4 Short To Supply!
P3-4 Short To Supply?
P3-6 Short To Supply?
Disconnect plug P3. If fault clears there is a problem with the wiring from P3-4 or P3-6 to the rest of the vehicle.
Armguard Active!
Elevation Switch Shifted?
Elevation Switch Stuck?
If the 23 flash code is triggered by armguard, it will occur once then clean. This is not a true fault but just an indica-
tion of the reason for the vehicle stop. If the 21 or 22 flash code is triggered by a fault with the elevation switch, it
will not clear. Check that the elevation switch correctly opens/closes when the platform is raised/lowered.
P3-4 Short To 0V?
P3-6 Short To 0V?
Disconnect plug P3. If fault clears there is a wiring fault from P3-4 or P3-6 to the rest of the vehicle.
Invalid Load - Check Sensors
Check the voltage out of the pressure transducer, into P4-2. It should be between 0.5V (zero pressure) and 4.5V
(maximum pressure) and should vary as the platform load & position varies.
Waiting For B+ on P2-12
B+ Supply Too Low
P4-1 Or P5-1 Short To 0V?
Check that the battery voltage is not too low.
Verify battery voltage on P2-12.
Disconnect plug P4 – if the fault clears there is a wiring fault from P4-1 to the rest of the vehicle.
SJIII Series
63
62
61
55
56
54
52
42
44
46
23
21
22
43
45
45
52
51
41
Service and Maintenance
SKYJACK, Page 13