UPS Control
This page lists the automatic switching and shutdown parameters.
UPS Output Shutdown Delay
This field allows the user to configure or view the delay (in seconds) of the UPS switching from the Run
(Inverter) mode to the Output Shutdown mode after receiving the Output Shutdown command. The UPS
output shutdown delay time count down will be synchronized with the output shutdown delay time setting
in the RemotEye II Shutdown Service program for all connected clients. (Up to 32 clients may be
connected simultaneously.) To avoid improper output shutdown of the clients, the UPS output shutdown
delay time setting in the RemotEye II should always be greater than the RemotEye II Shutdown Service
program's shutdown delay setting. Please refer to RemotEye II manual for instruction on how to setup
RemotEye II Shutdown Service.
Set UPS to Output Shutdown Mode after Delay (option)
This option switches the UPS from the Run (Inverter) mode to the Output Shutdown mode.
UPS Run (Inverter) Mode Delay
This field allows the administrator to configure or view the duration (in minutes) of the UPS switching from
the Output Shutdown mode to the Run (Inverter) mode after receiving the Run (Inverter) command.
Set UPS to Run (Inverter) Mode after Delay (option)
This option switches the UPS from Output Shutdown mode to the Run (Inverter) mode.
Set UPS to Run (Inverter) Mode AND Cancel Any Impending Shutdown (option)
This option cancels any impending shutdown to the UPS and set the UPS to Run (Inverter) mode.
Switch UPS between Stop (Bypass) Mode and Run (Inverter) Mode (option)
This option switches the UPS between the Run (Inverter) mode and the Bypass or Stop mode.
UPS Auto Start after Input Power Recovery Control
This field allows the administrator to enable or to disable the auto start feature of the UPS. Enabled, this
control will switch the UPS system to Run (Inverter) after power recovery from power failure.
UPS Auto Retransfer Control (option)
This field allows the administrator to enable or to disable the auto retransfer feature of the UPS. Enabled,
this control will switch the UPS system to Run (Inverter) after UPS recovered from fault alarms.
UPS Cold Start Control (option)
This field allows the administrator to enable or to disable the Cold Start feature of the UPS. Enabled, this
control, allows the administrator to start up using battery power when no input AC is available.
UPS Load Shed Control (option)
This field allows the administrator to enable or to disable the load shed feature of the UPS. When
enabled, the UPS load shed level is reached, the UPS will shutdown the low priority load, to conserve
power for more critical load.
UPS Load Shed Level (%) (option)
This field allows the administrator to set the level of load shed. When the level is reached and load shed
control is enabled, UPS will shutdown the low priority load, to conserve power for more critical load.
UPS Shed Relay off Delay (secs) (option)
This field allows the administrator to set the delay in seconds for the low priority load shutdown.
UPS Fan Speed (option)
The fans in the 1700 Series will operate at any of four different speeds depending on the environment
and system conditions. In the first stage the fans are off. As the load and or the ambient temperature
increase the fans will subsequently go to low, medium or high speed as required.
RemotEye II User Manual – 50024-014