GE MM300 Instruction Manual page 138

Motor management system low voltage motor protection and control
Hide thumbs Also See for MM300:
Table of Contents

Advertisement

CONFIGURATION SETPOINTS
NOTE:
NOTE
NOTE:
NOTE
5–28
Reset TCU Using Reset key
Range: Disabled/Enabled
Default: Enabled
If set to "Enabled", when a Lockout Reset is used to reset a Thermal Overload, the
Thermal Capacity % will be reset to zero.
Note that the RESET button of the GCP and BCP can be used to send a 'Lockout Reset
command' or a 'Thermal Capacity Reset' command. If the RESET button is pressed for
less than 10 seconds, a 'Lockout Reset' or 'Non-Lockout Reset' is sent. However, by
pressing the RESET button for more than 10 seconds, a 'Reset Thermal Capacity'
command is sent.
When a GCP/BCP reset key is pressed continuously for longer than 12 seconds the
Thermal Capacity % will be reset to zero, independently of the Reset TCU Using Reset Key
setting configuration.
Change Mode When Running
Range: Disabled/Enabled
Default: Enabled
If set to "Enabled," the Auto/Manual mode can be changed while the motor is running.
Set Date
Set to program today's date.
Set Time
Set to program current time.
Time Offset from UTC
Range: -24 to +24 step 0.25
Default: 0.00
Enter the time in hours that your zone is off from Universal Time.
Daylight Savings
Range: Disabled/Enabled
Default: Disabled
Set to enable automatic time change based on the DS time setpoints.
Once this setting is enabled all the Daylight Savings (DST) settings need to be configured to
valid values and not left in the "Not Set" state.
Orange LED Intensity
Range: 1 to 6
Default: 1
Selects brightness level (1 to 6) for Control Panel LEDs.
Green LED Intensity
Range: 1 to 6
Default: 1
Selects brightness level (1 to 6) for Control Panel LEDs.
Red LED Intensity
Range: 1 to 6
Default: 1
Selects brightness level (1 to 6) for Control Panel LEDs.
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS