User Interface Specifications; Metering And Monitoring Specifications; Control Specifications - GE MM300 Instruction Manual

Motor management system low voltage motor protection and control
Hide thumbs Also See for MM300:
Table of Contents

Advertisement

SPECIFICATIONS

User interface specifications

Metering and monitoring specifications

Control specifications

1–8
UNDERPOWER
Pickup level:........................................................... 1 to 100% of kW rating in steps of 1
Time delay:............................................................ 1 to 60 seconds in steps of 1
Timing accuracy:................................................ ±500 ms
Elements: ................................................................ trip and alarm
VOLTAGE PHASE REVERSAL
Configuration: ...................................................... ABC or Rev starter
Timing accuracy:................................................ ±500 ms
Elements: ................................................................ trip or alarm
GRAPHICAL CONTROL PANEL AND HAND HELD DEVICE
Size: ........................................................................... width 153mm, height 102mm, depth 35mm
LCD: ........................................................................... 3.5-inch color, 320 by 240 pixels
LED indicators: ..................................................... 10 LEDs
Pushbuttons:......................................................... Start A, Start B, Stop, plus 11 LCD screen display control keys
Ports:......................................................................... USB 2.0 port for laptop computer connection
Cable - GCP to Base Unit:................................ Shielded RJ45; Maximum length 6' (1.83 m)
BASIC CONTROL PANEL
Size: ........................................................................... BCP: width 75mm, height 75mm, depth 31mm
LCD: ........................................................................... 3.5-inch color, 320 by 240 pixels
LED indicators: ..................................................... 12 LEDs
Pushbuttons:......................................................... Start A, Start B, Stop, Reset, Auto, Manual
Cable - BCP to Base Unit:................................ Shielded RJ45; Maximum length 6' (1.83 m)
EVENT RECORDER
Capacity:................................................................. 256 events
Data storage:........................................................ non-volatile memory
FREQUENCY METERING
Range:...................................................................... 40.00 to 70.00 Hz in steps of 0.01
Accuracy: ............................................................... ±0.05 Hz
POWER METERING
Real power range: .............................................. –2000.0 to 2000.0 kW in steps of 0.1
Apparent power range:.................................... 0.0 to 2500.0 kVA in steps of 0.1
Accuracy: ............................................................... ±1% of full scale
POWER FACTOR METERING
Range:...................................................................... –0.99 to +0.99 in steps of 0.01
Accuracy: ............................................................... ±0.05
UNDERVOLTAGE RESTART
Dropout/Pickup Level: ...................................... 60 to 100% NCV in steps of 1%
Short Dip Time: .................................................... 100 to 500 ms or OFF in steps of 10 ms
Medium Dip Time: .............................................. 0.1 to 10.0 s in steps of 0.1 s
Medium Dip Delay: ............................................ 0.2 to 90 s in steps of 0.2 s
Long Dip Time:..................................................... 0.5 to 60.0 min or OFF in steps of 0.5 min
Long Dip Delay: ................................................... 1.0 to 1200.0 s in steps of 1.0 s
Short Dip Time Accuracy:............................... ±5% of total time
Medium and Long Dip Time Accuracy:.... ±1 s or ±5% of total time, whichever is greater
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTION

Advertisement

Table of Contents
loading