GE MM300 Instruction Manual page 45

Motor management system low voltage motor protection and control
Hide thumbs Also See for MM300:
Table of Contents

Advertisement

CHAPTER 2: INSTALLATION
NOTE:
NOTE
NOTE:
NOTE
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
Figure 2-29: Full-voltage non-reversing starter control wiring - IO_E
AC
Control Power
GE Multilin
Low Voltage
Manager
The above drawing applies only to a high-voltage power supply. If a low-voltage (DC)
power supply is used, an appropriate DC voltage source must be used for this power
supply.
.
The full-voltage non-reversing starter type is a full voltage or across-the-line non-reversing
starter.
When a start control is received, the pre-contactor relay (if any) is picked up for the set pre-
contactor time. When the pre-contactor timer times out, relay1 picks up and seals-in,
picking up contactor M, which starts the motor. When a stop control is received, relay1
drops out, contactor M drops out, and the motor stops. The pre-contactor is omitted on
forced starts (for example, UVR Immediate, External Start).
Connect AUX VT to the Control Supply for correct operation of the UV Restart feature and
correct input readings.
C14
PSU
C13
C12
C11
C10
C9
MM300
C8
C7
Motor
C6
C5
C4
C3
C2
C1
STARTER TYPES
Low Voltage
DC Suppl to
IO T pe E
-
+
Reset
Field Start
Field Stop
M
M
853704B3.cdr
2–25