Cooling Rate - GE MM300 Instruction Manual

Motor management system low voltage motor protection and control
Hide thumbs Also See for MM300:
Table of Contents

Advertisement

CHAPTER 5: SETPOINTS
PICKUP
STANDARD CURVE MULTIPLIERS
(× FLA)
× 1
× 2
× 3
4.00
5.83
11.66
17.49
4.25
5.12
10.25
15.37
4.50
4.54
9.08
13.63
4.75
4.06
8.11
12.17
5.00
3.64
7.29
10.93
5.50
2.99
5.98
8.97
6.00
2.50
5.00
7.49
6.50
2.12
4.24
6.36
7.00
1.82
3.64
5.46
7.50
1.58
3.16
4.75
8.00
1.39
2.78
4.16

Cooling rate

MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
× 4
× 5
× 6
× 7
23.32
29.15
34.98
40.81
20.50
25.62
30.75
35.87
18.17
22.71
27.25
31.80
16.22
20.28
24.33
28.39
14.57
18.22
21.86
25.50
11.96
14.95
17.94
20.93
9.99
12.49
14.99
17.49
8.48
10.60
12.72
14.84
7.29
9.11
10.93
12.75
6.33
7.91
9.49
11.08
5.55
6.94
8.33
9.71
The following tables illustrate the relation between GE Multilin MM2 and MM3 curve
numbers, NEMA curves, and the MM300 curve multipliers.
Table 5-2: MM2 and MM3 curve numbers and MM300 curve multipliers
MM2 and MM3 curve number
MM300 curve multiplier
Table 5-3: NEMA curves and MM300 curve multipliers
NEMA curve
MM300 curve multiplier
The model causes the thermal capacity used to decrease exponentially when the steady-
state thermal capacity used value is less than the actual thermal capacity used. This
simulates motor cooling. As a stopped motor normally cools significantly slower than a
running motor, the relay has two cooling time constant setpoints, one used when the
motor is off (stopped, tripped, locked out, pre-contactor, etc.), the other used when the
motor is on (starting, running, stopping). In each case, the time constant is time in minutes
for the motor temperature to cool by 63% of the difference between the initial
temperature and ambient temperature.
Figure 5-30: Thermal model cooling following a trip at t = 0
100%
75%
50%
25%
0%
× 8
× 9
× 10
× 11
46.64
52.47
58.30
64.13
41.00
46.12
51.25
56.37
36.34
40.88
45.42
49.97
32.44
36.50
40.55
44.61
29.15
32.79
36.43
40.08
23.91
26.90
29.89
32.88
19.99
22.48
24.98
27.48
16.96
19.08
21.20
23.32
14.57
16.39
18.21
20.04
12.66
14.24
15.82
17.41
11.10
12.49
13.88
15.27
1
2
3
1
2
3
Class 10
Class 15
4
6
Cool time constant = 30 minutes
0
30
60
90
Time (minutes)
PROTECTION ELEMENTS
× 12
× 13
× 14
69.96
75.79
81.62
61.50
66.62
71.75
54.51
59.05
63.59
48.66
52.72
56.77
43.72
47.36
51.01
35.87
38.86
41.85
29.98
32.48
34.97
25.44
27.55
29.67
21.86
23.68
25.50
18.99
20.57
22.15
16.65
18.04
19.43
4
5
6
7
4
7
9
12
Class 20
Class 30
8
12
120
150
180
853732A1.CDR
× 15
87.45
76.87
68.14
60.83
54.65
44.84
37.47
31.79
27.32
23.74
20.82
8
15
5–39

Advertisement

Table of Contents
loading

Table of Contents