Mixing Valve Motor - Viessmann vitotronic 200-h Installation And Service Instructions Manual

Weather-compensated, digital heating circuit control units
Table of Contents

Advertisement

Components

Mixing Valve Motor

Mixing valve "Open"

Mixing valve "Closed"
Legend
A Mixing valve plug
B Field wiring
C Connection to mixing valve adaptor
76
Vitotronic 200-H, HK1B Installation and Service
Components:
H Mixing valve motor (not for flanged mixing valve)
H Connecting plug for the heating circuit pump
H Supply temperature sensor as contact temperature
sensor for measuring the supply temperature, with
connecting cable 19 ft. (5.8 m) long.
Changing the rotational direction (if required)
1. Insert 3-pin plug A in the mixing valve motor
rotated through 180°.
2. Check the rotational direction.
Manual mixing valve adjustment
Lift the motor lever, unhook the mixing valve handle
and pull plug A.
Specification mixing valve motor
Rated voltage
Rated frequency
Power consumption
Permissible ambient temperature
H during operation
H during storage and
transport
120V~
60 Hz
4 W
32 to 104° F (0 to +40° C)
-4 to 149° F (-20 to +65° C)

Hide quick links: