Code 2

Calling up Coding Level 2

Note:
H In coding level 2, all codes are accessible, including the
codes from coding level 1.
H Codes that have no function due to the heating system
equipment level or the setting of other codes are not
displayed.
H The heating circuits are referred to below as "Heating
circuit 1" "Heating circuit 2" or "Heating circuit 3".
If the heating circuits were given individual
designations, the selected designation and "HC1",
"HC2" or "HC3" appear instead.

"General" Group

"General" Group
Coding
Coding in the factory set condition
00:1
One system circuit M1 (heating circuit 1),
without DHW heating.
Value address 00: ... Designation
2
3
4
5
6
7
8
9
10
* With an extension module for circuits 2 & 3 (optional accessory)
54
One heating circuit M1 (heating circuit 1)
with DHW heating (automatic recognition)
One heating circuit with mixing valve M2 (heating circuit 2)*
without DHW heating (automatic recognition)
One heating circuit with mixing valve M2 (heating circuit 2)*
with DHW heating (automatic recognition)
2 heating circuits with mixing valve M1 (heating circuit 1) and M2 (heating circuit 2)*
without DHW heating (automatic recognition)
2 heating circuits with mixing valve M1 (heating circuit 1) and M2 (heating circuit 2)*
with DHW heating (automatic recognition)
2 heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3)*
without DHW heating (automatic recognition)
2 heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3*
with DHW heating (automatic recognition)
3 heating circuits with mixing valve M1 (heating circuit 1), M2 (heating circuit 2) and
M3 (heating circuit 3)*
without DHW heating (automatic recognition).
3 heating circuits with mixing valve M1 (heating circuit 1), M2 (heating circuit 2) and
M3 (heating circuit 3)*
with DHW heating (automatic recognition).
Vitotronic 200-H, HK1B Installation and Service
1. Press OK and
simultaneously for approx. 4 sec.
2. Press OK and
simultaneously for approx. 4 sec.
3. "Coding level 2"
4. Select group of required coding address:
H "General"
H "DHW"
H "Solar"
H "Heating circuit 1/2*/3*"
H "All codes standard unit"
In this group, all coding addresses (except the
coding addresses from the "Solar" group) are
displayed in ascending order.
5. Select coding address.
6. Select value according to the following tables and
confirm with "OK".
7. If you want to reset all codes to their factory set
condition:
Select "Standard setting" in "Coding level 2".
Note: This also resets codes from coding level 1.
* With an extension module for circuits 2 & 3
(optional accessory)
Possible change
00:2
For system schemes, see the following table.
to
00:10