Weather-compensated, digital heating circuit control units
Table of Contents

Advertisement

Code 2

"DHW" Group

Coding in the factory set condition
55:0
DHW tank heating, hysteresis ± 2.5 K.
56:0
Set DHW temperature adjustable from
50 to 140° F (10 to 60° C).
57:0
With LON communication module:
No DHW demand to central DHW tank.
58:0
Without auxiliary function for DHW heating.
59:0
DHW tank heating:
Set start point –2.5 K
Set stop point +2.5 K
5A:0
No function
60:20
During DHW heating, the boiler water
temperature is up to 20 K higher than the
set DHW temperature.
62:10
Circulation pump with a run-on time after DHW
tank heating of max. 10 min.
64:2
During party mode and after external
changeover to constant operation with the
standard room temperature:
Constant DHW heating enabled and DHW
circulation pump "ON".
60
Vitotronic 200-H, HK1B Installation and Service
Possible change
55:2
DHW tank temperature control with 2 DHW tank
temperature sensors (see page 44).
55:3
DHW tank temperature control, primary store
system (see page 44).
56:1
Set DHW temperature adjustable from 50 to 203° F
(10 to 95° C).
Note: Observe the max. permissible
DHW temperature.
Change temperature controller at the boiler
control unit if required.
57:1
DHW demand to central DHW tank.
58:10
Input of a second set DHW temperature,
to
adjustable from 50 to 203° F (10 to 95° C)
58:60
(observe coding addresses "56" and "63").
59:1
Start point adjustable from 1 to 10 K below set
to
value.
59:10
5A:1
For DHW heating:
The set supply temperature is determined by
the DHW tank supply temperature demand.
Scan of the temperature in the "Diagnosis" menu,
"General" ("Common dem. temp"), see page 31.
60:10
The differential between the common supply
to
temperature and the set DHW temperature
60:50
is adjustable from 10 to 50 K.
62:0
Circulation pump without run-on.
62:1
Run-on time adjustable from 1 to 15 min.
to
62:15
64:0
No DHW heating, DHW circulation pump "OFF".
64:1
DHW heating and DHW circulation pump
according to time program.