Vitotronic 200-H, HK1B Installation and Service
"General" Group
Coding in the factory set condition
Participant number
77:10
LON participant number.
Detached house/apartment building
7F:1
Detached house
General
8F:0
Operation in the standard menu and extended
menu enabled.
Note: The respective code is only activated when
you exit the service menu (see page 81).

"DHW" Group

Coding
Coding in the factory set condition
DHW
67:40
For solar DHW heating:
Set DHW temperature 104° F (40° C).
Reheating is suppressed above the selected
set temperature (DHW heating by the boiler
only if solar energy is not sufficient).
Enable DHW circulation pump
73:0
DHW circulation pump:
"ON" according to time program.
(continued)
Possible change
77:1
LON participant number,
to
adjustable from 1 to 99:
77:99
1 - 4 = boiler control unit
5 = Cascade control unit
10 - 98 = Vitotronic 200-H
99 = Vitocom LAN1
Note: Each number must only be assigned
once.
7F:0
Apartment building
Separate adjustment of holiday program and
time program for DHW heating possible.
8F:1
Operation in the standard menu and extended
menu blocked.
8F:2
Operation enabled in the standard menu;
blocked in the extended menu.
Possible change
67:0
No set value 3.
67:10
Set DHW temperature adjustable from 50
to
to 203° F (10 to 95° C) (limited by boiler
67:95
specific parameters).
Observe the setting of coding address "56"
in the "DHW" group.
73:1
"ON" from once per hour for 5 min up to
to
6 times per hour for 5 min. during the time
73:6
program.
73:7
Constantly "ON".
Code 1
49